Produktvergleich
UPS 1 [x] | UPS 2 [x] | UPS 3 [x] | |
Allgemeine Merkmale | |||
Model | |||
Main Picture | |||
Pictures | |||
Item Number | 10120120 | 10120120 | 10120120 |
EAN | 4260074974393 | 4260074974393 | 4260074974393 |
Features |
|
|
|
Typ | Online | Online | Online |
Kapazität | 1000VA / 900W | 1000VA / 900W | 1000VA / 900W |
Ausgangsleistungsfaktor | 0.90 | 0.90 | 0.90 |
Eingang | |||
Eingangsspannungsbereich | 120-276 VAC Depends on Load Level | 120-276 VAC Depends on Load Level | 120-276 VAC Depends on Load Level |
Max THDi | ≤5% | ≤5% | ≤5% |
Eingangsleistungsfaktor | ≥ 0.99 at full load | ≥ 0.99 at full load | ≥ 0.99 at full load |
Frequenzbereich | 45Hz - 55Hz or 54Hz - 66Hz | 45Hz - 55Hz or 54Hz - 66Hz | 45Hz - 55Hz or 54Hz - 66Hz |
Frequenz (Synchronisationsbereich) | 45Hz - 55Hz or 54Hz - 66Hz | 45Hz - 55Hz or 54Hz - 66Hz | 45Hz - 55Hz or 54Hz - 66Hz |
Output | |||
Ausgangsnennspannung | 208/220/230/240 VAC | 208/220/230/240 VAC | 208/220/230/240 VAC |
Reine Sinuswelle | Ja | Ja | Ja |
THDv | ≤2% Full Linear Load; ≤5% Non-Linear Load | ≤2% Full Linear Load; ≤5% Non-Linear Load | ≤2% Full Linear Load; ≤5% Non-Linear Load |
Spannungsregelung (Bat. Mod.) | ±1% | ±1% | ±1% |
Frequency (Battery Mode) | ±0,2Hz | ±0,2Hz | ±0,2Hz |
Technische Details | |||
Load Crest Ratio | 3:1 | 3:1 | 3:1 |
Transfer Time [AC to Battery] | 0ms | 0ms | 0ms |
Transfer Time [Inverter to Bypass] | 0ms | 0ms | 0ms |
Transfer Time [Inverter to ECO] | 1ms | 1ms | 1ms |
Transfer Time [ECO to Inverter] | <10ms (7-8ms typical) | <10ms (7-8ms typical) | <10ms (7-8ms typical) |
Bypass | Before UPS Power-on: Default “No” Change to “Yes” via display panel Overload und UPS Failure: Automatically transfer to bypass By Setting: Voltage Rang: 120-276V ± 3% | Before UPS Power-on: Default “No” Change to “Yes” via display panel Overload und UPS Failure: Automatically transfer to bypass By Setting: Voltage Rang: 120-276V ± 3% | Before UPS Power-on: Default “No” Change to “Yes” via display panel Overload und UPS Failure: Automatically transfer to bypass By Setting: Voltage Rang: 120-276V ± 3% |
Generator-Unterstützung | Ja | Ja | Ja |
Überlastfähigkeit | 12s @102%-130%; 1.5s @130%-150%; 100ms @ >150% | 12s @102%-130%; 1.5s @130%-150%; 100ms @ >150% | 12s @102%-130%; 1.5s @130%-150%; 100ms @ >150% |
Externer Akkuanschluss | Ja | Ja | Ja |
Ladegerät | 1.5A | 1.5A | 1.5A |
Fan Logic | Always on, automatic speed control | Always on, automatic speed control | Always on, automatic speed control |
LCD Indicators | UPS status, Load level, Battery level, Input/Output voltage, AC mode, battery mode, Bypass mode, fault conditions; LCD Display colour : Blue, red, red flashing (depends on UPS status), direction swappable (rack/tower) | UPS status, Load level, Battery level, Input/Output voltage, AC mode, battery mode, Bypass mode, fault conditions; LCD Display colour : Blue, red, red flashing (depends on UPS status), direction swappable (rack/tower) | UPS status, Load level, Battery level, Input/Output voltage, AC mode, battery mode, Bypass mode, fault conditions; LCD Display colour : Blue, red, red flashing (depends on UPS status), direction swappable (rack/tower) |
Effizienz | |||
Netzmodus Vollast | 88.2% | 88.2% | 88.2% |
BATTERY mode full Load | 85.0% | 85.0% | 85.0% |
Energy Star compliance | Compliant with requirement in ECO Mode | Compliant with requirement in ECO Mode | Compliant with requirement in ECO Mode |
Batterien und Überbrückungszeit | |||
Akkus | 3x 12V/7Ah | 3x 12V/7Ah | 3x 12V/7Ah |
DC Spannung | 3 x 12V | 3 x 12V | 3 x 12V |
Recharge Time | 3h to 90% | 3h to 90% | 3h to 90% |
Full Load Backup Time | 5min | 5min | 5min |
Half Load Backup Time | 16min | 16min | 16min |
Anschlüsse und Kommunikation | |||
IEC C13 Outlet | 8 | 8 | 8 |
Programmable Outlets | 8 | 8 | 8 |
Eingang | C14 | C14 | C14 |
Software | WinPower | WinPower | WinPower |
USB port | Ja | Ja | Ja |
HID-Unterstützung | Ja | Ja | Ja |
RS-232 Port | Ja | Ja | Ja |
Extension Slot | Ja | Ja | Ja |
Dry Contacts | Ja | Ja | Ja |
EPO Port | Ja | Ja | Ja |
Umgebung | |||
Geräuschpegel | < 45dB | < 45dB | < 45dB |
Temperatur | 0°C – 40°C | 0°C – 40°C | 0°C – 40°C |
Luftfeuchtigkeit | 0% - 95% RH (non-condensing) | 0% - 95% RH (non-condensing) | 0% - 95% RH (non-condensing) |
IEC 62040-3 Klassifizierung | VFI-SS-311 | VFI-SS-311 | VFI-SS-311 |
Logistik | |||
Packungsinhalt | UPS, Manual, USB Cable, Input Power Cable, 2x IEC Cable, RS-232 Cable, Tower holder, Rack Ears, EPO Plug, Dry Contacts Plug | UPS, Manual, USB Cable, Input Power Cable, 2x IEC Cable, RS-232 Cable, Tower holder, Rack Ears, EPO Plug, Dry Contacts Plug | UPS, Manual, USB Cable, Input Power Cable, 2x IEC Cable, RS-232 Cable, Tower holder, Rack Ears, EPO Plug, Dry Contacts Plug |
Sprache Bedienungsanleitung | EN/DE/FR/RU/PL | EN/DE/FR/RU/PL | EN/DE/FR/RU/PL |
Breite | 438mm | 438mm | 438mm |
Höhe | 86.5mm | 86.5mm | 86.5mm |
Tiefe | 436mm | 436mm | 436mm |
Gewicht | 16.2kg | 16.2kg | 16.2kg |
Verpackung - Breite | 535mm | 535mm | 535mm |
Verpackung - Höhe | 215mm | 215mm | 215mm |
Verpackung - Tiefe | 535mm | 535mm | 535mm |
Verpackung - Gewicht | 19.2kg | 19.2kg | 19.2kg |